Yes, but the heat will still likely need boosting by about a further 10 degrees either at the source or end user.

DC inlet is 45°C, outlet is 55°C assuming a 10°C ΔT. By the time that's travelled 500m–1km through pipework you've lost a few degrees, so you're arriving at the HIU at maybe 50–52°C. The home radiator circuit then takes that down by around say 12°C, returning ~38°C. Factor in pipe losses on the return leg and you're back at the data centre with maybe 35°C inlet rather than 45°C — meaning the DC output is now only 45°C rather than 55°C, and the whole system gradually degrades each cycle. You could address this by mixing some hot output back into the return to keep the DC inlet stable at 45°C, but eh.


Replies

KaiserProtoday at 10:00 AM

> By the time that's travelled 500m–1km through pipework you've lost a few degrees

you'd be surprised. If you have high flow, and the pipes are insulated and underground, then after about a week the temperature drop isn't that much. You do have heat losses, but if you have a high enough continuos flow and a big enough pipe, then it'll be low enough to not worry about, especially if the aim is heat shedding rather than efficiency.

My old flat was powered by both the 1970s boilers across the way, and more recently the massive south london incinerator. The pipe cross section was I think 40cm and at peak carried ~3-5 Megawatts of heat. I think it operated at 150c, but that could be me misremembering (this is the later version of the network: https://www.burohappold.com/projects/veolia-southwark-2-0-he... for the councils is they get a maintained heater network, which is much cheaper than doing it themselves (even more now with gas being so expensive) the power station gets to charge for a waste product and it doubles their on paper efficiency, its a win win.)

show 1 reply
superluserdoyesterday at 11:40 PM

>Factor in pipe losses on the return leg and you're back at the data centre with maybe 35°C inlet rather than 45°C

Surely having the input fluid being colder is a benefit, not a problem? Just run the fluid more slowly through the system?

show 1 reply