> You'd have to deal with additional wiring losses due to the lower voltage between the central rectifier and the devices

No. Everybody always complains about voltage drop. It's not a problem with LED lighting loads because they use so much less power. Let me prove it to you.

Assume we use the same 14-gauge copper Romex for our 48VDC lighting circuit that is already inside most home walls in the USA.

DC resistance of 14-gauge copper wire: 0.002525 ohms per foot.

Voltage drop over a circuit:

  Current x Ohms/foot x Two-way distance
  --------------------------------------
               Nominal Voltage
Assume we're driving a 13-watt LED bulb (typical 100W incandescent equivalent) that is 50 feet from the supply.

Current would be 13w/48v = 270mA.

  .270A x 0.002525Ohms/foot x 100feet
  -----------------------------------
            48v

  = 0.00142V
So the voltage drop is 0.14%. Any voltage drop less than 3% is considered acceptable by NEC.

Oh, but what if I want to run more than one bulb? Fine, let's do 10 bulbs on the same 14-gauge supply wire. Now the voltage drop is 1.4%. Still less than half the maximum limit.

And this is 14-gauge wire. What about 12-gauge? Well, that's 0.001588 ohms/foot.

  .270 x 0.001588 x 100
  ---------------------
           48
Now for 10 bulbs the voltage drop is eight tenths of a percent.

Running LED room lighting in a standard American house at 48VDC on the 14-gauge wire that's already in the walls is completely doable.

Yes, we still need constant-current supplies in or near the bulbs, and those are not 100% efficient. Keep in mind also that some of that 13 watts we assumed above is for typical Home Depot 120VAC bulbs that have builtin rectifiers and [probably] crappy power supplies, so the waste power used by the constant-current supplies I'm talking about here -- which are simpler than the supplies used in Home Depot bulbs -- is probably less.