What fraction of a typical data center’s power usage comes from the chillers?


Replies

KaiserPro • yesterday at 4:40 PM

Depends on the datacentre.

for "traditional" datacenters, its up to half. Ie you put in one megawatt and then spend a megawatt to move that heat outside. (although its never quite that bad, you need to spec it for the hottest day in that area + 10%)

If you use evaporative cooling, then you cut your cooling bill significantly (ie top up chillers plus cooling loop pumps)